Aerial insulated cable with rated voltage of 10KV and 35KV
1、 Rated voltage: 10KV 、35KV.
2、 Cable installation temperature: not less than -20℃.
3、 Maximum rated temperature
XLPE insulated cable: The maximum operating temperature of cores shall not exceed 90℃ when the cable is used for long period. The temperature of cores shall not exceed 250℃ at short circuit (the max. Duration dose not exceed 5 seconds). HDPE insulated cable: The maximum operating temperature of cores shall not exceed 75℃ when the cable is used for long period. The temperature of cores shall not exceed 150℃ at short circuit(the max. Duration dose not exceed 5 seconds).
4、 The permissible bending radius of cable shall not be less then 20(D+d) mm (D and d represent the nominal overall diameter of cable and conductor respectively).
The cable is manufactured according to GB14049 and enterprise standards.
The cable is suitable to aerial power lines with AC rated voltage U(Um) of 10(12)KV and 35(42KV) for transmitting electricity.
Operating characteristics:
Current rating of XLPE aerial insulated cable with rated voltage of 10KV |
Nominal cross-sectionalarea of conductor |
Cu conductor |
Al conductor |
Nominal cross-sectionalarea of conductor(mm2) |
Cu conductor |
Al conductor |
25 35 70 95 |
174 211 255 393
|
134 164 198 304 |
120 150 185 300 |
454 520 600 824 |
352 403 465 639 |
All sorts of this s include:
Name:al conductor light XLPE insulated aerial cable |
|
Model:JKLYJ/Q1*95 |
Size: |
Nominal Cross-sectional: |
Rated voltage:10Kv
Dark Fiber:1
|
Use:This is English word
|
Parameter
|
Nominal cross-sectional area | Nominal thickness of insulation | Approx overall diameter | Max,resistance of conductor at 20℃ | Approx weight of cable | 35 | 2.5 | 12.0 | 0.868 | 184.41 | 50 | 2.5 | 13.3 | 0.641 | 231.35 | 70 | 2.5 | 15.0 | 0.443 | 296.8 | 95 | 2.5 | 16.6 | 0.320 | 381.2 | 120 | 2.5 | 18.0 | 0.253 | 462.7 | 150 | 2.5 | 19.6 | 0.206 | 557.9 | 185 | 2.5 | 21.2 | 0.164 | 666.1 | 240 | 2.5 | 23.4 | 0.125 | 829.1 | 300 | 2.5 | 25.6 | 0.100 | 1010.3 |
|